AL101-1-R-SL

Indoor Single Alarm Panel

 

Electrical Specifications

  • 120 VAC, 60 Hz, 180mA
  • Switch input at terminals 3 & 4
  • Relay Output at terminals 5 & 6 & 7
    • Contact rating: 10A
  •  Wire Gauge Range is 20-10AWG
  •  Buzzer — 95 dB @ 1 ft.

Description

AL101 Overfill Protection Device, Indoor Alarm
Part No.: AL101-1-R-SL Indoor Single Alarm Panel

The Model AL101-1-R-SL is an Indoor alarm panel that accepts a switch contact input and provides an audible alarm signal/strobe light when the external contact is closed. A red lighted push-button provides the visual alarm indication. The push-button is a momentary switch that, when pressed, mutes the buzzer/strobe light. In the event of a power failure the alarm/strobe light will come back on with the power. The red light remains on until the alarm condition is corrected. A relay contact output is available for the input switch. The alarm circuit resets automatically. It must be mounted in a non-hazardous location. Use Ktech float switches for the alarm input contacts.

 

Certifications

  • CAN/ULC-S661-10

Certified to CSA C22.2 No.205 and Conforms to UL2017